Fluke I430-FLEXI-TF - Flex Current Clamp

Flex Current Clamp

Fluke

Category : Accessories

by quote only Add to Cart

Documents:

Overview
Features
Information
Calibration

The i430 Flex is an AC current probe utilizing the Rogowski principle. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas, without batteries or an external power source.

Also available as a pack of 4 pieces of the i430 current clamp, to be used for high current measurements. The Flex clamp fits around bus bars and large or hard-to-reach conductors. This 4-pack is perfect for use with 3-phase tools such as the Fluke 430 series.

General Specifications
Probe and Cable Material
   TPE rubber, reinforced insulation
   UL94 V-0, Colour: RED Munsell 7.5
   R 1/14
Couplings Material
   Polypropylene, UL94 V-0
Probe Cable Length
   610 mm
Probe Cable Diameter
   12.4 mm
Probe Cable Bend Radius
   40 mm
Output cable length
   2.5 meters RG58
Output Connector
   Safety BNC Connector
Operating Range
   -20 to +90°C
Storage Temperature
   -40 to +105°C
Operating Humidity
   15% to 85% (non condensing)
Degree of protection (Probe)
   IP41

 

Specifications
Current Range
   3000 A AC RMS
Voltage output (@1000 ARMS, 50 Hz)
   85 mV
Accuracy
   ± 1% of reading
   (@ 25°C, 50 Hz)
Linearity (10% to 100% of range)
   ± 0.2% of reading
Noise (10 Hz – 7 kHz)
   1.0 mV ACRMS
Output impedance
   82 Ω min
Load Impedance
   50 kΩ
Internal Resistance per 100 mm probe length
   10.5Ω ± 5%
Bandwidth (-3dB)
   10 Hz to 7 kHz
Phase Error (45 – 65 Hz)
   ±1°
Position Sensitivity
   ± 2% of reading max.
Temperature Coefficient
   ± 0.08% max of reading per °C
Working Voltage (see Safety Standards section)
   1000 V AC RMS or DC (head)
   30 V max. (output)

 

Safety Specifications
Safety Standards
   BS EN 61010-1 2001
   BS EN 61010-2-032 2002
   BS EN 61010-031 2002, 1000 VRMS, Category III, Pollution Degree 2
   Use of the probe on uninsulated conductors is limited to 1000 V ACRMS or DC and frequencies below 1 kHz.
   Please note that this probe is designed to work with Fluke 435, if used with other products
   safety rating for the output to earth is limited to 600V ACRMS or DC.

 


Do you have a Flex Current Clamp that needs to be calibrated?

We offer standard traceable calibration and ISO 17025 accredited calibration services.

Get your Flex Current Clamp calibrated today! Click Here!