Test Products International 714 - Combustion Effincy Analyzer with NOX and Optional PC Interface
The carbon monoxide sensor used in TPI combustion efficiency analyzers feature an on-board filter capable of filtering NO (nitric oxide), NO2 (nitrogen dioxide) and NOX (combination of NO and NO2) to prevent cross sensitivity errors.
Use TPI analyzers to test flue gases in gas and oil fired equipment including high efficiency furnaces and condensing boilers. Measure CO, O2, and stack temperature.
Determine combustion efficiency, CO2, and CO air free. Some models include built-in differential manometer, combustible gas detection, PC communication, data logging, and can measure NO / NOX.
- Measure 02, CO, and NOX
- Calculate CO2, NOX, efficiency, excess air
- Measure 02, CO, and NOX
- Calculate CO2, NOX, efficiency, excess air
| Carbon Monoxide (CO) Measurement | Range 0 to 10,000 ppm Resolution 1 ppm Accuracy +/-5ppm or 5% of reading whichever is greater |
| Oxygen (02) Measurement |
Range 0 to 25% |
| Carbon Dioxide (CO2) | Range 0 to 25% Resolution 0.1% Calculated Value |
| Nitric Oxide Measurement | Range 0 to 5,000ppm Resolution 1ppm Accuracy <100ppm: ±5ppm <1000ppm ±5% >1000ppm: ±10ppm |
| NOX Measurement | Range 0 to 5,250 Resolution 1ppm Calculated Value |
| Temperature Measurement | Range -40 to 1472°F, or -40 to 800°C Resolution 1°F or °C Accuracy (K-type) ±0.3%, ±2°F or ±1°C |
| Draft/Pressure Measurement |
Selectable Ranges mBar,kPa, and inH2O |
| Gross/Net Efficiency |
Range 0 to 100% |
| CO/CO2 Ratio | Range 0 to 0.999 Resolution 0.001 Calculated Value |
| Combustible Gas Level Indication | Yes (For flue gasses) |
| Operating Temperature | 14°F to 122°F (-10°C to 50°C) |
| Charger Input Voltage | 110V to 230V (50/60Hz) |
| Selectable Fuels | Natural Gas, LPG, Light Oil, Heavy Oil, Bituminous Coal, Anthracite Coal, Coke, Butane, Wood, Bagasse |
| Display Type | Backlit 3 line LCD |
| Data Storage | 10 Locations |
| Data Logging | Yes (5 Pages) |
| Print Capability | Yes, via optional IR printer (A740) |
| PC Communication | Yes via optional IR adapter (A767) |
| Date & Time Function | 24 Hour Real Time Clock |
| Dimensions | 200mm x 90mm x 60mm |
| Weight | 500g |
| Conformity | BS7927 (and the draft BS7967) |
Do you have a Combustion Effincy Analyzer with NOX and Optional PC Interface that needs to be calibrated?
We offer standard traceable calibration and ISO 17025 accredited calibration services.
Get your Combustion Effincy Analyzer with NOX and Optional PC Interface calibrated today! Click Here!
There are currently no reviews for this product.
Recommended Accessories for the Combustion Effincy Analyzer with NOX and Optional PC Interface
![]()
Adapter tubing
![]()
Static Tip
![]()
Gas Valve Pressure Adapter