Test Products International 715 - High CO (above 10,000ppm carbon monoxide) Combustion Analyzer with Built-in Differential Thermometer, Differential Manometer, and NO Measurement & NOX Calculation
The carbon monoxide sensor used in TPI combustion efficiency analyzers feature an on-board filter capable of filtering NO (nitric oxide), NO2 (nitrogen dioxide) and NOX (combination of NO and NO2) to prevent cross sensitivity errors.
Use TPI analyzers to test flue gases in gas and oil fired equipment including high efficiency furnaces and condensing boilers. Measure CO, O2, and stack temperature.
Determine combustion efficiency, CO2, and CO air free. Some models include built-in differential manometer, combustible gas detection, PC communication, data logging, and can measure NO / NOX.
Use the optional A784 flow regulator to reduce the flow rate of the gas being sampled to measurable levels on high pressure systems such as gas compression engines. The A784 is included in the 715K3 kit.
The TPI 715 Gas Analyser is a state of the art, easy to use analyser designed not only to display and calculate the required readings from a flue but also to cover most of the other desirable parameters associated with combustion. The instrument is ruggedly constructed and comes with a 3 Year Guarantee.
Your TPI 715 Gas Analyser comes complete with the following items as standard:
- TPI 714 Instrument
- Rubber Boot
- Soft Carrying Case
- Sampling Probe (c/w Type “K” Thermocouple)
- In-Line Filter
- Exhaust Spigot (removable)
- Instruction Manual
Your TPI 715 Flue Gas Analyser has the following options available:
- Various Temperature Probes (see Appendix B)
- Infrared Printer A740B
| Model 715 Specifications | ||
|---|---|---|
| Carbon Monoxide (CO) Measurement | Range 0 to 9.999% Resolution .001% Accuracy +/-5ppm or 5% of reading whichever is greater |
|
| Oxygen (02) Measurement | Range 0 to 25% Resolution 0.1% Accuracy ±0.3% |
|
| Carbon Dioxide (CO2) | Range 0 to 25% Resolution 0.1% Calculated Value |
|
| Nitric Oxide Measurement | Range 0 to 5,000ppm Resolution 1ppm Accuracy <100ppm: ±5ppm <1000ppm ±5% >1000ppm: ±10ppm |
|
| NOX Measurement | Range 0 to 5,250 Resolution 1ppm Calculated Value |
|
| Temperature Measurement | Range -40 to 1472°F, or -40 to 800°C Resolution 1°F or °C Accuracy (K-type) ±0.3%, ±2°F or ±1°C |
|
| Draft/Pressure Measurement | Selectable Ranges mBar,kPa, and inH2O Ranges -150 mBar to +150 mBar -15 kPa to +15 kPa -60 inH2O to +60 in H20 Resolution 0.001 inH2O Accuracy ±0/5% fsd |
|
| Gross/Net Efficiency | Range 0 to 100% Resolution 0.1% Calculated Value |
|
| CO/CO2 Ratio | Range 0 to 0.999 Resolution 0.001 Calculated Value |
|
| Combustible Gas Level Indication | Yes (For flue gasses) | |
| Operating Temperature | 14°F to 122°F (-10°C to 50°C) | |
| Charger Input Voltage | 110V to 230V (50/60Hz) | |
| Selectable Fuels | Natural Gas, LPG, Light Oil, Heavy Oil | |
| Display Type | Backlit 3 line LCD | |
| Data Storage | 10 Locations | |
| Data Logging | N/A | |
| Print Capability | Yes, via optional IR printer (A740) | |
| PC Communication | N/A | |
| Date & Time Function | 24 Hour Real Time Clock | |
| Dimensions | 200mm x 90mm x 60mm | |
| Weight | 500g | |
| Conformity | BS7927 (and the draft BS7967) | |
Do you have a High CO (above 10,000ppm carbon monoxide) Combustion Analyzer with Built-in Differential Thermometer, Differential Manometer, and NO Measurement & NOX Calculation that needs to be calibrated?
We offer standard traceable calibration and ISO 17025 accredited calibration services.
Get your High CO (above 10,000ppm carbon monoxide) Combustion Analyzer with Built-in Differential Thermometer, Differential Manometer, and NO Measurement & NOX Calculation calibrated today! Click Here!
There are currently no reviews for this product.
Recommended Accessories for the High CO (above 10,000ppm carbon monoxide) Combustion Analyzer with Built-in Differential Thermometer, Differential Manometer, and NO Measurement & NOX Calculation
![]()
Carrying Case
![]()
Mini pump protection filter
![]()
Flue Probe