Metrel MI3309 BT - DeltaGT PAT Tester
The MI 3309 DeltaGT lightweight design, pre-programmed and custom test sequences, optional QR / Barcoding, android keyboard application and RFID systems make the MI 3309 an ideal instrument for high volume professional safety testing of portable appliances.
Standards Applied
- EN 61557
- VDE 0404-1
- VDE 0404-2
- VDE 0701-0702
- NEN 3140
- BS COP
- Autosequencing
- Dual powered
- PASS / FAIL
- Fixed appliance testing
- Leakage and load currents with (optional) current clamp
- Scan and test
- RFID
- RCD testing
- Memory
- Built-in charger & rechargeable batteries
- Android application
- PC SW PATLink PRO
- PC SW PATLink PRO Plus
Earth Continuity (200 mA in to 2.00Ω)
| Range | Resolution | Accuracy |
|
0.00 Ω … 19.99 Ω |
0.01 Ω |
±(5 % of reading + 3 digits) |
|
20.0 Ω … 199.9 Ω |
0.1 Ω |
Indication only |
|
200 Ω … 1999 Ω |
1 Ω |
Indication only |
Insulation resistance, Insulation – S resistance (250 VDC, 500 VDC)
| Range | Resolution | Accuracy |
|
0.00 MΩ … 19.99 MΩ |
0.01 MΩ 0.1 MΩ 0.1 MΩ |
±(5 % of reading + 3 digits) |
|
20.0 MΩ … 49.9 MΩ |
0.01 MΩ 0.1 MΩ 0.1 MΩ |
±(5 % of reading + 3 digits) |
|
50.0 MΩ … 199.9 MΩ |
0.01 MΩ 0.1 MΩ 0.1 MΩ |
Indication only |
Differential leakage current (230 VAC)
| Range | Resolution | Accuracy |
|
0.00 mA … 19.99 mA |
0.01 mA |
±(5 % of reading + 5 digits) |
Substitute leakage current (30 VAC)
| Range | Resolution | Accuracy |
|
0.00 mA … 9.99 mA |
0.01 mA 0.1 mA |
±(5 % of reading + 3 digits) |
|
10.0 mA … 20.0 mA |
0.01 mA 0.1 mA |
±(5 % of reading + 3 digits) |
Touch leakage current (230 VAC)
| Range | Resolution | Accuracy |
|
0.00 mA … 7.00 mA |
0.01 mA |
±(10 % of reading + 5 digits) |
(P)RCD testing (10 mA, 15 mA, 30 mA)
| Range | Resolution | Accuracy |
|
0 ms … 300 ms (½xIΔN) |
0.1 ms |
±3 |
|
0 ms … 300 ms (IΔN) |
0.1 ms |
±3 |
|
0 ms … 40 ms (5xIΔN) |
0.1 ms |
±1 ms |
Power measurement (230 VAC)
| Range | Resolution | Accuracy |
|
0.00 kVA … 4.00 kVA |
0.01 kVA |
±(5 % of reading + 3 digits) |
Voltage TRMS measurement
| Range | Resolution | Accuracy |
|
80 V ... 300 V |
1 V |
±(2 % of reading + 2 digits) |
Clamp current
| Range | Resolution | Accuracy |
|
0.00 mA ... 9.99 mA |
0.01 mA |
±(5 % of reading + 10 digits) |
|
10.00 mA ... 99.9 mA |
0.1 mA |
±(5 % of reading + 5 digits) |
|
100 mA ... 999 mA |
1 mA |
±(5 % of reading + 5 digits) |
|
1.00 A .... 9.99 A |
0.01 A |
±(5 % of reading + 5 digits) |
|
10.0 A ... 16.0 A |
0.1 A |
±(5 % of reading + 5 digits) |
General Specifications
|
Polarity test |
Test voltage < 50 VAC |
|
Power supply |
6 x 1.2 V NiMH rechargeable batteries, type AA; 230 V, 50 Hz / 60 Hz |
|
Overvoltage category |
CAT II / 300 V |
|
COM port |
RS232 and USB |
|
Dimensions |
140 x 80 x 230 mm |
|
Weight |
1.2 kg |