Fluke BT521 - Battery Analyzer

Battery Analyzer

Fluke

Rated 0 / 5 (0 reviews)

Category : Battery Analyzers

by quote only add to cart

Documents:
Datasheet

Overview
Features
Specifications
Calibration

Fluke 521 Series Battery Analyzer for Stationary Battery Systems

  • Battery Voltage – During the internal resistance test, Fluke Battery Analyzers also measure the voltage of the battery under test
  • Discharge Volts – The Discharge mode collects the voltage of each battery multiple times at a user defined interval during a discharge or load test. Users can calculate the time a battery takes to drop to the cut-off voltage and use this time to determine the capacity loss of the battery
  • Ripple Voltage Test – Measures unwanted residual ac component of the rectified voltage in dc charging and inverter circuits. Allows users to test ac components in dc charging circuits and find one of the root causes of battery deterioration
  • Meter and Sequence Modes – The Meter mode is used for a quick test or troubleshooting. In this mode you can save and read the readings in a measurement or time sequence. The Sequence mode is for maintenance tasks with multiple power systems and battery strings. Before a task starts, users can configure a profile for the task for data management and report generation
  • Threshold and Warning – Users can configure a maximum of 10 sets of thresholds and receive a Pass/ Warning/ Fail indication after each measurement
  • AutoHold – When AutoHold is turned on, a reading is captured when it remains stable for 1 second. The reading is then released when a new measurement starts
  • AutoSave – When AutoSave is turned on, measured values are saved to internal memory automatically after an AutoHold reading is captured
  • Fluke Battery Management Software – Easily import data from the Product to a PC. The measurement data and battery profile information is stored and archived with the Management Software and can be used for comparison and trend analysis. All measurement data, battery profile and analysis information can be used to easily generate reports
  • Comprehensive logging – All measured values are automatically captured during testing and can be reviewed on the instrument before downloading for on the-go analysis
  • Optimized user interface – Quick, guided setup ensures you're capturing the right data every time
  • Battery life – 7.4 V 3000 mAh lithium-ion battery for more than eight hours continuous operation.
  • USB port – For fast data download to supplied data analysis and report management application software.
  • Highest safety rating in the industry – CAT III 600 V, 1000 V dc max. rated for safe measurements all around the battery power supply equipment.
  • BTL21 Intelligent Test Probes with long and short extenders, built-in LCD display and speaker for visual and audio feedback and integrated infrared temperature sensor for taking temperature measurements on the negative battery post with every test
  • Wireless capability works with Fluke Battery Analyze mobile app (Fluke BA Mobile)*
    • View profile and associated test results from the Battery Analyzer
    • Send out the profile and test results via Email with (.csv) data format
Functions Range Resolution Accuracy BT510 BT520 BT521
Battery resistance1 3 mΩ 0.001 mΩ 1% + 8
30 mΩ 0.01 mΩ 0.8% + 6
300 mΩ 0.1 mΩ 0.8% + 6
3000 mΩ 1 mΩ 0.8% + 6
VDC 6 V 0.001 V 0.09% + 5
60 V 0.01 V 0.09% + 5
600 V 0.1 V 0.09% + 5
1000 V 1 V 0.09% + 5    
VAC (45 Hz to 500 Hz with 800 Hz filter) 600 V 0.1 V 2% + 10
Frequency (displayed with VAC and AAC)2 500 Hz 0.1 Hz 0.5% + 8
AC voltage ripple (20 KHz  Max) 600 mV 0.1 mV 3% + 20
6000 mV 1 mV 3% + 10
ADC/AAC (with accessory Fluke i410) 400 A 1 A 3.5% + 2    
Temperature 0°C to 60°C 1°C 2°C (4°F)    
Meter mode 999 records for each measurement position with time stamp
Sequence mode Up to 100 profiles and 100 profile templates (Each profile stores up to 450 batteries) with time stamp
1. The measurement is based on AC injection method. The injected source signal is < 100 mA, 1 kHz.
2. Trigger level VAC: 10 mV, AAC: 10 A
Measurement Modes BT510 BT520 BT521      
Resistance (mΩ)      
Battery voltage      
Voltage DC      
Voltage AC and frequency  (Hz)      
Ripple volt      
Temperature of negative battery post          
DC and AC current (and frequency)          
DMM mode      
Sequence mode        
Discharge measurement mode      
Automatic measurement  save      
Wireless commumcation          
Memory view      
General Specifications
Size (H x W x D) 22 x 10.3 x 5.8 cm (9 x 4 x 2 in)
Weight 850 g (1.9 lb)
Screen dimensions 7.7 x 5.6 cm (3 x 2.2 in)
Interface USB mini
Warranty 3 years
Environment Specifications
Operating temperature 0°C to 40°C
Storage temperature -20°C to 50°C
Lithium-ion  battery charging temperature 0°C to 40°C
Operating humidity Non-condensing (10°C)
≤ 80% RH (at 10°C to 30°C)
≤ 75% RH (at 30°C to 40°C)
Operating altitude Sea level to 2000 meters
Storage altitude Sea level to 12,000 meters
IP rating IP40
Radio FCC Class A
Vibration  requirements MIL-PRF-28800F: Class 2
Drop test  requirements 1 meter
Temperature coefficients Add 0.1 x specified accuracy for each degree C above 28°C or below 18°C
Safety  compliance 600 V CAT III
EMC IEC 61326
ROHS China, Europe
Protection class 2 Pollution Degree II
Battery compliance UN38.3
UL2054
IEC62133
2 G per IEC68-2-26, 25 G, and 29

Do you have a Battery Analyzer that needs to be calibrated?

We offer standard traceable calibration and ISO 17025 accredited calibration services.

Get your Battery Analyzer calibrated today! Click Here!

 