Soken DAC-ASM-7 30kV - C & tanδ Automatic Measuring Set (30kV)
Overview
Features
Specifications
Calibration
DAC-ASM-7 has been designed to perform dielectric dissipation factor (tanδ) measurement in wide ranges: Capacitance 100pF - 10μF, tanδ 0 - 100%. Test voltage is from AC100V to 12kV with CT&Cs box type (DAC-CCB-7). DAC-ASM-7 can measure both grounded and ungrounded specimens preciously and safely, and is ideal for development test, inspection test, and preventive maintenance on equipments, such as Generators, Motors, Transformers, and insulating materials.
- Capacitance Range : 100pF - 10μF
- Test Voltage : AC100V - 30kV
- Internal Standard Capacitor (CT&Cs BOX)
- Grounded Specimen(GST)or Ungrounded Specimen(UST)can be selected.
| Test Voltage | AC 0.10kV – 30kV |
| Frequency | 50/60Hz |
| Minimum Resolution | Capacitance 0.1pF (1nF range) tanδ 0.001% (2% range) |
Measuring Range
| Capacitance | 0.1nF – 10uF (GST mode) 0.1nF – 1uF (UST mode) |
| tanδ(%) | 0 – 100 (%), 3 ranges |
| P.F (%) | 0 – 70.7 (%), 3 ranges |
| Voltage Meter | 0 – 18kV one range |
| Current Meter | 0 – 50A Auto 6 ranges |
Accuracy
| Capacitance | ±(5%Rdg+2digits) ±(5%Rdg+5digits) at less than 1nF |
| tanδ(%) / P.F(%) | ±(0.02%+3%Rdg+2digits) ±(0.04%+5%Rdg+5digits) at less than 1nF. |
| Voltage Meter | ±5% (mean) |
| Current Meter | ±5% (mean) |
| Input Voltage | AC100-240V ±10% 50/60Hz |
| Interface | GP-IB |
| Size & Weight | W430 x D385 x H200 mm, (without projections) Approx. 15kg |
| Accessories | Measuring Cable (for UST)x1,10m CT Connecting Cable x 1, 5m CS Connecting Cable x 1, 5m Grounding Cable x 1, 5m GND Connecting Cable x 1, 5m AC Cable x 1, 2m (Measuring Cable (GST) is not included) |
CT & Cs Unit
| Model | DAC-CCB-6 (Tank Type) |
| Filled Gas | SF6 (0.2MPa) |
Built-in CT
| Max Rated Voltage | 30kV |
| Max Rated Current | 50A : range 1uF/10uF(GST) 1A : range 100nF/10nF/1nF 1/10 of Maximum rating on continuous test. 120% of Maximum rating on 15 min test |
Measuring standard Capacitor
| Max Rated Voltage | 30kV |
| Nominal Capacitance | 1000pF±10% |
| tanδ | <0.05% |
| Size & Weight | W347 x D347 x H617mm Approx. 40kg (Without projections) |
Do you have a C & tanδ Automatic Measuring Set (30kV) that needs to be calibrated?
We offer standard traceable calibration and ISO 17025 accredited calibration services.
Get your C & tanδ Automatic Measuring Set (30kV) calibrated today! Click Here!